| Battery type |
Lead-acid or lithium-ion |
| Battery voltage range |
40-60 V |
| Max. charge/discharge current |
120 A |
| Charging strategy for lithium battery |
Automatic adaptation to BMS |
| Number of battery inputs |
1 |
| Max. connected PV power |
10,000 W |
| Max. PV input power |
8,000 W |
| Max. PV input voltage |
500 V |
| Start-up voltage |
125 V |
| MPPT voltage range |
150-425 V |
| Nominal PV input voltage |
370 V |
| Max. PV operating current |
18+18 A |
| Max. short-circuit current, input |
27+27 A |
| Number of MPPT / strings per MPPT |
2/1+1 |
| Nominal AC input/output power |
5,000 W |
| Max. AC input/output power (VA) |
5,500 VA |
| Nominal AC input/output current |
22.7/21.7 A |
| Max. AC input/output current |
25/23.9 A |
| Max. continuous AC pass-through (grid to load) |
35 A |
| Peak power (island mode) |
2 × nominal power for 10 s |
| Nominal input/output voltage |
220V/230V 0.85Un-1.1Un L+N+PE |
| Nominal grid frequency / range |
50/45-55, 60/55-65 Hz |
| Power factor, adjustment range |
0.8 leading – 0.8 lagging |
| Total harmonic distortion (THDi) |
<3% (of nominal power) |
| DC injection current |
<0.5% In |
| Max. efficiency |
97.6% |
| Euro efficiency |
96.5% |
| MPPT efficiency |
>99% |
| Built-in protection |
DC reverse polarity protection, AC output overcurrent protection, thermal protection, AC output overvoltage protection, AC output short-circuit protection, DC component monitoring, arc fault detection (AFCI) (optional), islanding protection, DC switch, insulation monitoring, residual current monitoring |
| Overvoltage protection |
Type II (DC), Type II (AC) |
| Display |
LCD display |
| Communication interface |
WiFi, RS485, CAN |
| Operating temperature |
-40 to +60°C, >45°C power derating |
| Permissible humidity |
0~100% |
| Max. installation altitude |
2,000m |
| Noise level |
<45 dB |
| Protection rating (IP) |
IP65 |
| Inverter topology |
Non-isolated (solar), isolated (battery) |
| Overvoltage category |
OVC II (DC), OVC III (AC) |
| Dimensions (W×H×D) |
330×580×232 (excl. connectors and brackets) |
| Weight |
24.9 kg |
| Warranty |
5 years / 10 years (warranty period depends on the inverter's installation location – see Deye's warranty policy) |
| Cooling |
Intelligent air cooling |
| Grid standards |
IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 |
| Safety / EMC standards |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |