| Battery type |
Lithium-ion |
| Battery voltage range |
160-700 V |
| Max. charging current |
75 A |
| Max. discharging current |
75 A |
| Charging strategy for lithium battery |
Automatic adaptation to BMS |
| Number of battery inputs |
1 |
| Max. connected PV power |
60,000 W |
| Max. PV input power |
48,000 W |
| Max. PV input voltage |
1,000 V |
| Start-up voltage |
180 V |
| MPPT voltage range |
150-850 V |
| Rated PV input voltage |
600 V |
| Max. short-circuit current, input |
54+54+54 A |
| Max. PV operating current |
36+36+36 A |
| Number of MPPT / strings per MPPT |
3/2+2+2 |
| Rated AC input/output power |
30,000 W |
| Max. AC input/output power (VA) |
33,000 VA |
| Peak power (off-grid) |
1.5 × rated power for 10 s |
| Rated AC input/output current |
45.5/43.5 A |
| Max. AC input/output current |
50/47.9 A |
| Max. continuous AC pass-through (grid to load) |
80 A |
| Rated input/output voltage |
220/380V, 230/400V 0.85Un-1.1Un |
| Grid connection |
3L+N+PE |
| Rated grid frequency / range |
50/45-55, 60/55-65 |
| Power factor, adjustment range |
0.8 capacitive – 0.8 inductive |
| Total harmonic distortion (THDi) |
<3% (of rated power) |
| DC injection current |
<0.5% ln |
| Max. efficiency |
98.50% |
| Euro-efficiency |
98.0% |
| MPPT efficiency |
>99% |
| Built-in protection |
DC reverse polarity protection, AC output overcurrent protection, thermal protection, AC output overvoltage protection, AC output short-circuit protection, DC component monitoring, arc fault detection (AFCI) (optional), anti-islanding protection, DC switch, insulation monitoring, residual current monitoring |
| Surge protection |
Type II (DC), Type II (AC) |
| Communication interface |
RS485/RS232/CAN |
| Monitoring |
GPRS/WiFi/Bluetooth/4G/LAN (optional) |
| Operating temperature |
-40°C to +60°C, >45°C power derating |
| Permissible humidity |
0-100% |
| Max. installation altitude |
3,000m |
| Noise level |
≤ 55 |
| Protection class (IP) |
IP65 |
| Inverter topology |
Non-isolated |
| Overvoltage category |
OVC II (DC), OVC III (AC) |
| Dimensions (W×H×D) |
448x688x270 (excluding connectors and brackets) |
| Weight |
46 kg |
| Warranty |
5 years / 10 years (warranty period depends on the installation site of the inverter – see Deye's warranty policy) |
| Cooling |
Intelligent air cooling |
| Grid standards |
IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 |
| Safety / EMC standards |