| Battery type |
Lithium-ion |
| Battery voltage range |
160-1000 V |
| Max. charge/discharge current |
100+100 A |
| Lithium battery charging strategy |
Automatic adaptation to BMS |
| Number of battery inputs |
2 |
| Max. connected PV power |
250,000 W |
| Max. PV input power |
200,000 W |
| Max. PV input voltage |
1,000 V |
| Start-up voltage |
180 V |
| MPPT voltage range |
150-850 V |
| Rated PV input voltage |
650 V |
| Max. PV operating current |
42+42+42+42+42+42+42+42+42+42 A |
| Max. short-circuit current, input |
63+63+63+63+63+63+63+63+63+63 A |
| Number of MPPT / strings per MPPT |
10/2+2+2+2+2+2+2+2+2+2 |
| Rated AC input/output power |
125,000 W |
| Max. AC input/output power (VA) |
135,000 VA |
| Rated AC input/output current |
189.4/181.2 A |
| Max. AC input/output current |
204.6/195.7 A |
| Max. continuous AC pass-through (grid to load) |
250 A |
| Peak power (off-grid) |
1.5 × rated power for 10 s |
| Power factor, adjustment range |
0.8 leading – 0.8 lagging |
| Rated input/output voltage |
220/380V, 230/400V 0.85Un-1.1Un 3L+N+PE |
| Rated grid frequency / range |
50/45-55, 60/55-65 |
| Total harmonic distortion (THDi) |
<3% (at rated power) |
| DC injection current |
<0.5%In |
| Max. efficiency |
98.70% |
| Euro-efficiency |
98.10% |
| MPPT efficiency |
>99% |
| Built-in protection |
DC reverse polarity protection, AC output overcurrent protection, thermal protection, AC output overvoltage protection, AC output short-circuit protection, DC component monitoring, arc fault detection (AFCI) (optional), anti-islanding protection, DC switch, insulation monitoring, residual current monitoring |
| Surge protection |
Type II(DC), Type II(AC) |
| Display |
LCD display+LED |
| Communication interface |
RS485/RS232/CAN |
| Monitoring |
GPRS/WiFi/Bluetooth/4G/LAN (optional) |
| Operating temperature |
-40°C–+60°C, >45°C power derating |
| Permissible humidity |
0-100% |
| Max. installation altitude |
3,000m |
| Noise level |
≤ 65 |
| Ingress protection (IP) |
IP65 |
| Inverter topology |
Non-isolated |
| Overvoltage category |
OVC II(DC), OVC III(AC) |
| Dimensions (W×H×D) |
734×1091×344 (excl. connectors and brackets) |
| Weight |
161.7 kg |
| Warranty |
5 years / 10 years (warranty period depends on the inverter's installation location – see Deye's warranty policy) |
| Cooling |
Intelligent air cooling |
| Grid standards |
IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 |
| Safety / EMC standards |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |